Diesel fuel begins to deteriorate as soon as it is
produced. This problem poses no threat if the fuel is
consumed quickly. Unfortunately, diesel fuel may be
stored for years. This deterioration affects the fuels
pumpability and combustibility. Aged fuel tends to
repolymerize, forming submicron particles, causing
excessive wear to injector pumps, clogged filters and
sludge deposits.
By recirculating your fuel stores, you can fight the
contamination battle by constantly recirculating the
fuel and removing water, dirt, and algae before it
builds up and poses a threat to your equipment. When
your fuel is free from contaminants, your equipment will
show increased reliability and performance, as clean
fuel burns cleaner.
The
FRS 660 Series of fuel
recirculating systems are pre-engineered, integrated
systems consisting of a packaged pump, motor,
programmable control and pre-plumbed and pre-wired
accessories. The RCI Fuel Recirculating Systems provide
the user with the reliability of a job-engineered
system, matched components, and factory assembly. These
systems are designed for use with fuel oil (class II or
class III combustible liquids having a flash point of
100 Degrees F or higher).
The
RCI FRS 660 Systems are
fully enclosed and suitable for wall or pad mounting.
All devices, wiring, electrical, and plumbing are
contained within a NEMA 4 UL listed weatherproof
enclosure. Isolated internal compartments are provided
for mechanical and electrical components. External ports
are provided for connection of field plumbing. The
enclosure includes a drip catch basin with internal and
external alarm and leak detection.
Routine circulation with the
FRS 660 Systems will
remove 100% of all free water and up to 99% of dust,
dirt and other normal and natural contaminates found in
all diesel fuels, including sludge and algae. In
addition to dramatically extending filter life and
improving engine performance, it increases
combustibility. Even today's "CLEAN" diesel fuel will
easily become contaminated during transportation and
storage. RCI Technologies Fuel
Purifiers contain no filters and no moving parts,
there are no elements or cartridges to clean, change or
replace.
Click here to see brochure for this product
|
 |
|
|
 |
Do
you really need to keep a Fuel Tank at 2 Microns?
There are vendors trying to
sell fuel recirculating systems, quoting "7 Stages of
filtration" or "Let us clean your 30,000 gallon fuel
tank to 2 Microns," without any consideration for the
end user. Do you realize how long you would have to run
the system to maintain a 30,000-gallon fuel tank at 2
microns? And how many times your customer would have to
change these 2-micron filters? If they can maintain
your fuel tank at 2 microns then there would be no need
for your inline filters. It just doesn't wash!
With the RCI Technologies
Fuel Purifier meeting and exceeding the "90 mesh
strainer coalescer/separator requirements," we can
design a system to any specification, but would be
negligent not to advise our customer of a potential
problem with this design. Diesel equipment has multiple
filters ranging in micron size to accommodate the
contamination found in all fuels. Most primary filters
are in the 10 to 20 micron size, sometimes as high as 30
micron. The secondary filter, or final filter, should
be 2 to 10 microns, thus reducing the chances of filter
clogging and excessive maintenance.
It would be cost
prohibitive for your customer to try to maintain a fuel
tank at 2 micron when going to a higher micron primary
filter. Conventional filtration is designed to shut off
the fuel flow as the filter clogs. Therefore, the
potential problem of having multiple filters from 2
micron to 30/20/10 back to 2 micron would not be cost
effective to your customer, as the cost of filter
replacement, down time, and hazardous waste disposal
fees constantly increase.
RCI Technologies Fuel
Purifier will remove all the water and
particulates to below 10 microns and requires
no replacement filters, cartridges or elements to clean,
change or replace. Total maintenance is a simple
purging. The sole function of our Purifier is to remove
water and particulate before it gets to
the conventional filtration. Here again, installing a 2
micron filter at the beginning of the fuel stream, would
cause your customer excessive maintenance and down time
changing the 2 micron filters.
In Section 3 of our FRS
Sales Manual, installation photos will show how some of
our valued customers, Home Savings & Loan (FTI) and
Exodus Communications (Earth-Safe), have used RCI
Technologies fuel purification products to protect their
expensive conventional tank cleaning systems,
recirculating systems, and day tanks, due to extreme
high cost of maintaining them.
We are proud to provide a
total maintenance system that requires only a simple
purging, providing your customer years of quality fuel
at minimal cost.
Robert Randle
President |
Available Models
|
Model FRS 660-2-UL
Designed for Single Tank
System / Rated at 2 GPM
Complete System is NEMA 4 UL 508A Listed
All closed cabinet models include the following
STANDARD features:
-
PLC
-
NEMA 4 UL 508A listed weatherproof
enclosure.
-
Powder coated white with key lock security.
-
6" weatherproof operator touch panel interface.
-
NPT brass inlet/outlet ball valves.
-
RCI Universal Fuel Purifier
Primary particulate
removal - 98% (to 10 microns.)
-
Free water removal -
99.9%.
-
Pre-engineered for Class II or III combustible
liquids.
-
Brass swing-check valves.
-
Manual key - auto / off / hand switch.
-
Common alarm reset button.
-
Common audible alarm.
-
System emergency shutdown points.
-
Recirculating pump with high pressure safety switch.
-
Water detector with Alarm and ball drain valve.
-
Catch basin leak detector.
-
Cabinet Leak Sensor and Alarm (Pump Shut Off.)
-
Magnetic Fuel Decontamination Unit.
-
Factory assembled, pre-plumbed and pre-wired.
-
Isolated compartments for
mechanical and electrical devices.
-
Expandable system.
Model FRS 660-2-UL STANDARD Features :
-
36" x 36" x 12" Cabinet.
-
275 lbs. - Estimated shipping weight.
-
1/2" NPT Brass Inlet/Outlet Ball Valves.
-
1/2" NPT Brass Swing Check Valves.
-
FP 700 - RCI Universal Fuel Purifier.
2 GPM.
-
Pump Motor Starter - 20
amp single pole circuit breaker.
-
1/3 H.P., 115-208/230 VAC Single Phase, 60 Hz. motor
ODP.
PLC.
Options/Upgrades:
-
15 gallon waste tank and
alarm.
-
Automatic water drain into 15 gallon
container w/high level alarm.
-
3 Micron Spin - On Filter 1/2" NPT w/gauge.
-
3 Micron Spin - On Filter 1" NPT w/gauge.
-
Ethernet - PLC module, operator interface & 5 port.
-
Ethernet - field retrofit operation PLC module,
operator interface & 5 port.
-
Purifier heater.
-
Main disconnect breaker w/rotary handle (250)
(UL 508A w/42k
interrupt capacity.)
-
Main disconnect breaker w/rotary handle (480)
(UL 508A w/42k
interrupt capacity.)
-
MODBUS output.
-
Non-fused main disconnect switch w/rotary handle.
-
Secondary containment interface.
-
Strip heater for controller.
-
Thermostatically controlled system heater (touch pad,
controller purifier.)
-
Upgrade to 480VAC, 3 phase power.
-
115/120 Volt - 60 Hz.
-
208 Volt - 1 Phase - 60 Hz.
-
230 Volt - 1 Phase - 60 Hz.
-
208 Volt - 3 Phase - 60 Hz.
-
230 Volt - 3 Phase - 60 Hz.
-
380 Volt - 3 Phase - 50 Hz.
-
480 Volt - 3 Phase - 60
Hz.
|

|
|
Model FRS 660-2-OF-UL
Designed for Single Tank
System / Rated at 2 GPM
Complete System is NEMA 4 UL 508A Listed
All open face models include the following STANDARD
features:
-
PLC
-
NEMA 4 UL 508A listed weatherproof
enclosure.
-
Powder coated white with key lock security.
-
6" weatherproof operator touch panel interface.
-
NPT brass inlet/outlet ball valves.
-
RCI Universal Fuel Purifier
-
Pre-engineered for Class II or III combustible
liquids.
-
Brass swing-check valves.
-
Manual key - auto / off / hand switch.
-
Common alarm reset button.
-
Common audible alarm.
-
System emergency shutdown points.
-
Recirculating pump with high pressure safety switch.
-
Water detector with Alarm and ball drain valve.
-
Catch basin leak detector.
-
Cabinet Leak Sensor and Alarm (Pump Shut Off.)
-
Magnetic Fuel Decontamination Unit.
Factory assembled, pre-plumbed and pre-wired.
-
Isolated compartments for
mechanical and electrical devices.
-
Expandable system.
Model FRS 660-2-OF-UL STANDARD Features :
-
36" x 36" x 12" Cabinet.
-
240 lbs. - Estimated shipping weight.
-
1/2" NPT Brass Inlet/Outlet Ball Valves.
1/2" NPT Brass Swing Check Valves.
-
FP 700 - RCI Universal Fuel Purifier.
-
2 GPM.
-
Pump Motor Starter - 20
amp single pole circuit breaker.
-
1/3 H.P., 115-208/230 VAC Single Phase, 60 Hz. motor
ODP.
Options/Upgrades:
-
15 gallon waste tank and
alarm.
-
Automatic water drain into 15 gallon
container w/high level alarm.
-
3 Micron Spin - On Filter 1/2" NPT w/gauge.
-
3 Micron Spin - On Filter 1" NPT w/gauge.
-
Ethernet - PLC module, operator interface & 5 port.
-
Ethernet - field retrofit operation PLC module,
operator interface & 5 port.
Purifier heater.
-
Main disconnect breaker w/rotary handle (250) (UL 508A w/42k
interrupt capacity.)
-
Main disconnect breaker w/rotary handle (480) (UL 508A w/42k
interrupt capacity.)
-
MODBUS output.
-
Non-fused main disconnect switch w/rotary handle.
-
Secondary containment interface.
-
Strip heater for controller.
-
Thermostatically controlled system heater (touch pad,
controller purifier.)
-
Upgrade to 480VAC, 3 phase power.
-
115/120 Volt - 60 Hz.
-
208 Volt - 1 Phase - 60 Hz.
-
230 Volt - 1 Phase - 60 Hz.
-
208 Volt - 3 Phase - 60 Hz.
-
230 Volt - 3 Phase - 60 Hz.
-
380 Volt - 3 Phase - 50 Hz.
-
480 Volt - 3 Phase - 60
Hz.
|
 |
|
Model FRS 660-11-UL
Designed for Single Tank
System / Rated at 11 GPM
Complete System is NEMA 4 UL 508A Listed
All closed cabinet models include the following
STANDARD features:
-
PLC
-
NEMA 4 UL 508A listed weatherproof
enclosure.
-
Powder coated white with key
lock security.
-
6" weatherproof operator
touch panel interface.
-
NPT brass inlet/outlet ball valves.
-
RCI Universal Fuel Purifier
-
Primary particulate
removal - 98% (to 10 microns.)
-
Free water removal -
99.9%.
-
Pre-engineered for Class II
or III combustible
liquids.
-
Brass swing-check valves.
-
Manual key - auto / off /
hand switch.
-
Common alarm reset button.
-
Common audible alarm.
-
System emergency shutdown
points.
-
Recirculating pump with high
pressure safety switch.
-
Water detector with Alarm
and ball drain valve.
-
Catch basin leak detector.
-
Cabinet Leak Sensor and Alarm (Pump Shut Off.)
-
Magnetic Fuel Decontamination Unit.
-
Factory assembled, pre-plumbed and pre-wired.
-
Isolated compartments for
mechanical and electrical devices.
-
Expandable system.
Model FRS 660-11-UL Features :
-
48 " x 42 " x 12" Cabinet.
-
500 lbs. - Estimated shipping weight.
-
1" NPT Brass Inlet/Outlet Ball Valves.
-
1" NPT Brass Swing Check Valves.
-
FP 1000 - RCI Universal Fuel Purifier.
-
11 GPM.
-
Pump Motor Starter - 20
amp single pole circuit breaker.
-
1 H.P., 115-208/230 VAC Single Phase, 60 Hz. motor ODP.
Options/Upgrades:
-
15 gallon waste tank and
alarm.
-
Automatic water drain into 15 gallon
container w/high level alarm.
-
3 Micron Spin - On Filter 1/2" NPT w/gauge.
-
3 Micron Spin - On Filter 1" NPT w/gauge.
-
Ethernet - PLC module, operator interface & 5 port.
-
Ethernet - field retrofit operation PLC module,
operator interface & 5 port.
-
Purifier heater.
-
Main disconnect breaker w/rotary handle (250) (UL 508A w/42k
interrupt capacity.)
-
Main disconnect breaker w/rotary handle (480)
(UL 508A w/42k
interrupt capacity.)
-
MODBUS output.
-
Non-fused main disconnect switch w/rotary handle.
-
Secondary containment interface.
-
Strip heater for controller.
-
Thermostatically controlled system heater (touch pad,
controller purifier.)
-
Upgrade to 480VAC, 3 phase power.
-
115/120 Volt - 60 Hz.
-
208 Volt - 1 Phase - 60 Hz.
-
230 Volt - 1 Phase - 60 Hz.
-
208 Volt - 3 Phase - 60 Hz.
-
230 Volt - 3 Phase - 60 Hz.
-
380 Volt - 3 Phase - 50 Hz.
-
480 Volt - 3 Phase - 60
Hz.
|
|
|
Model FRS 660-11-OF-UL
Designed for Single Tank
System / Rated at 11 GPM
Complete System is NEMA 4 UL 508A Listed
All open face models include the following STANDARD
features:
-
PLC
-
NEMA 4 UL 508A listed weatherproof
enclosure.
-
Powder coated white with key lock security.
-
6" weatherproof operator touch panel interface.
-
NPT brass inlet/outlet ball valves.
-
RCI Universal Fuel Purifier
-
Pre-engineered for Class II or III combustible
liquids.
-
Brass swing-check valves.
-
Manual key - auto / off / hand switch.
-
Common alarm reset button.
-
Common audible alarm.
-
System emergency shutdown points.
-
Recirculating pump with high pressure safety switch.
-
Water detector with Alarm and ball drain valve.
-
Catch basin leak detector.
-
Cabinet Leak Sensor and Alarm (Pump Shut Off.)
-
Magnetic Fuel Decontamination Unit.
-
Factory assembled, pre-plumbed and pre-wired.
-
Isolated compartments for
mechanical and electrical devices.
-
Expandable system.
Model FRS 660-2-OF-UL STANDARD Features :
-
48" x 42 " x 12" Cabinet.
-
470 lbs. - Estimated shipping weight.
-
1" NPT Brass Inlet/Outlet Ball Valves.
-
1" NPT Brass Swing Check Valves.
-
FP 1000 - RCI Universal Fuel Purifier.
-
11 GPM.
-
Pump Motor Starter - 20
amp single pole circuit breaker.
-
1 H.P., 115-208/230 VAC Single Phase, 60 Hz. motor ODP.
Options/Upgrades:
-
15 gallon waste tank and
alarm.
-
Automatic water drain into 15 gallon
container w/high level alarm.
-
3 Micron Spin - On Filter 1/2" NPT w/gauge.
-
3 Micron Spin - On Filter 1" NPT w/gauge.
-
Ethernet - PLC module, operator interface & 5 port.
-
Ethernet - field retrofit operation PLC module,
operator interface & 5 port.
Purifier heater.
-
Main disconnect breaker w/rotary handle (250)
(UL 508A w/42k
interrupt capacity.)
-
Main disconnect breaker w/rotary handle (480)
(UL 508A w/42k
interrupt capacity.)
-
MODBUS output.
-
Non-fused main disconnect switch w/rotary handle.
-
Secondary containment interface.
-
Strip heater for controller.
-
Thermostatically controlled system heater (touch pad,
controller purifier.)
-
Upgrade to 480VAC, 3 phase power.
-
115/120 Volt - 60 Hz.
-
208 Volt - 1 Phase - 60 Hz.
-
230 Volt - 1 Phase - 60 Hz.
-
208 Volt - 3 Phase - 60 Hz.
-
230 Volt - 3 Phase - 60 Hz.
-
380 Volt - 3 Phase - 50 Hz.
-
480 Volt - 3 Phase - 60
Hz.
|
 |
|
Model FRS 660-25-UL
Designed for Single Tank
System / Rated at 25 GPM
Complete System is NEMA 4 UL 508A Listed
All closed cabinet models include the following
STANDARD features:
-
PLC
-
NEMA 4 UL 508A listed weatherproof
enclosure.
-
Powder coated white with key lock security.
-
6" weatherproof operator touch panel interface.
-
NPT brass inlet/outlet ball valves.
-
RCI Universal Fuel Purifier
-
Primary particulate
removal - 98% (to 10 microns.)
-
Free water removal -
99.9%.
-
Pre-engineered for Class II or III combustible
liquids.
-
Brass swing-check valves.
-
Manual key - auto / off / hand switch.
-
Common alarm reset button.
-
Common audible alarm.
-
System emergency shutdown points.
-
Recirculating pump with high pressure safety switch.
-
Water detector with Alarm and ball drain valve.
-
Catch basin leak detector.
-
Cabinet Leak Sensor and Alarm (Pump Shut Off.)
-
Magnetic Fuel Decontamination Unit.
-
Factory assembled, pre-plumbed and pre-wired.
-
Isolated compartments for
mechanical and electrical devices.
Expandable system.
Model FRS 660-11-UL Features :
-
48 " x 42 " x 12" Cabinet.
-
650 lbs. - Estimated shipping weight.
-
1" NPT Brass Inlet/Outlet Ball Valves.
-
1" NPT Brass Swing Check Valves.
-
FP 1000 - RCI Universal Fuel Purifier.
25 GPM.
-
Pump Motor Starter - 20
amp single pole circuit breaker.
-
1.5 H.P., 115-208/230 VAC Single Phase, 60 Hz. motor
ODP.
Options/Upgrades:
-
15 gallon waste tank and
alarm.
-
Automatic water drain into 15 gallon
container w/high level alarm.
-
3 Micron Spin - On Filter 1/2" NPT w/gauge.
-
3 Micron Spin - On Filter 1" NPT w/gauge.
-
Ethernet - PLC module, operator interface & 5 port.
-
Ethernet - field retrofit operation PLC module,
operator interface & 5 port.
Purifier heater.
-
Main disconnect breaker w/rotary handle (250)
(UL 508A w/42k
interrupt capacity.)
-
Main disconnect breaker w/rotary handle (480)
(UL 508A w/42k
interrupt capacity.)
-
MODBUS output.
-
Non-fused main disconnect switch w/rotary handle.
-
Secondary containment interface.
-
Strip heater for controller.
-
Thermostatically controlled system heater (touch pad,
controller purifier.)
-
Upgrade to 480VAC, 3 phase power.
115/120 Volt - 60 Hz.
-
208 Volt - 1 Phase - 60 Hz.
-
230 Volt - 1 Phase - 60 Hz.
-
208 Volt - 3 Phase - 60 Hz.
-
230 Volt - 3 Phase - 60 Hz.
-
380 Volt - 3 Phase - 50 Hz.
-
480 Volt - 3 Phase - 60
Hz.
|
|
|
Model FRS 660-MTU-UL
Designed for Single Tank
System / Rated at 11 GPM
Complete System is NEMA 4 UL 508A Listed
All closed cabinet models include the following
STANDARD features:
-
PLC
-
NEMA 4 UL 508A listed weatherproof
enclosure.
-
Powder coated white with key
lock security.
-
6" weatherproof operator
touch panel interface.
-
NPT brass inlet/outlet ball valves.
-
RCI Universal Fuel Purifier
-
Primary particulate
removal - 98% (to 10 microns.)
-
Free water removal -
99.9%.
-
Pre-engineered for Class II or III combustible
liquids.
-
Brass swing-check valves.
-
Manual key - auto / off / hand switch.
-
Common alarm reset button.
-
Common audible alarm.
-
System emergency shutdown points.
-
Recirculating pump with high pressure safety switch.
-
Water detector with Alarm and ball drain valve.
-
Catch basin leak detector.
-
Cabinet Leak Sensor and Alarm (Pump Shut Off.)
-
Magnetic Fuel Decontamination Unit.
-
Factory assembled, pre-plumbed and pre-wired.
-
Isolated compartments for
mechanical and electrical devices.
-
Expandable system.
Model FRS 660-11-UL Features :
-
48 " x 42 " x 12" Cabinet.
-
650 lbs. - Estimated shipping weight.
-
1" NPT Brass Inlet/Outlet Ball Valves.
-
1" NPT Brass Swing Check Valves.
-
FP 1000 - RCI Universal Fuel Purifier.
-
11 GPM.
-
Pump Motor Starter - 20
amp single pole circuit breaker.
-
1 H.P., 115-208/230 VAC Single
-
Phase, 60 Hz. motor ODP.
Options/Upgrades:
-
15 gallon waste tank and
alarm.
-
Automatic water drain into 15 gallon
container w/high level alarm.
-
3 Micron Spin - On Filter 1/2" NPT w/gauge.
-
3 Micron Spin - On Filter 1" NPT w/gauge.
-
Ethernet - PLC module, operator interface & 5 port.
-
Ethernet - field retrofit operation PLC module,
operator interface & 5 port.
Purifier heater.
-
Main disconnect breaker w/rotary handle (250)
(UL 508A w/42k
interrupt capacity.)
-
Main disconnect breaker w/rotary handle (480)
(UL 508A w/42k
interrupt capacity.)
-
MODBUS output.
-
Non-fused main disconnect switch w/rotary handle.
-
Secondary containment interface.
-
Strip heater for controller.
-
Thermostatically controlled system heater (touch pad,
controller purifier.)
-
Upgrade to 480VAC, 3 phase power.
-
115/120 Volt - 60 Hz.
-
208 Volt - 1 Phase - 60 Hz.
-
230 Volt - 1 Phase - 60 Hz.
-
208 Volt - 3 Phase - 60 Hz.
-
230 Volt - 3 Phase - 60 Hz.
-
380 Volt - 3 Phase - 50 Hz.
-
480 Volt - 3 Phase - 60
Hz.
|
|
|
Model FRS 660-MTU-OF-UL
Designed for Single Tank
System / Rated at 11 GPM
Complete System is NEMA 4 UL 508A Listed
All open face models include the following STANDARD
features:
-
PLC
-
NEMA 4 UL 508A listed weatherproof
enclosure.
-
Powder coated white with key
lock security.
-
6" weatherproof operator touch panel interface.
-
NPT brass inlet/outlet ball valves.
-
RCI Universal Fuel Purifier.
-
Pre-engineered for Class II or III combustible
liquids.
-
Brass swing-check valves.
-
Manual key - auto / off / hand switch.
-
Common alarm reset button.
-
Common audible alarm.
-
System emergency shutdown points.
-
Recirculating pump with high
pressure safety switch.
-
Water detector with Alarm and ball drain valve.
-
Catch basin leak detector.
-
Cabinet Leak Sensor and Alarm (Pump Shut Off.)
-
Magnetic Fuel Decontamination Unit.
-
Factory assembled, pre-plumbed and pre-wired.
-
Isolated compartments for
mechanical and electrical devices.
-
Expandable system.
Model FRS 660-11-UL Features :
-
48 " x 42 " x 12" Cabinet.
-
590 lbs. - Estimated shipping weight.
-
1" NPT Brass Inlet/Outlet Ball Valves.
-
1" NPT Brass Swing Check Valves.
-
FP 1000 - RCI Universal Fuel Purifier.
-
11 GPM.
-
Pump Motor Starter - 20
amp single pole circuit breaker.
-
1 H.P., 115-208/230 VIC Single Phase, 60 Hz. motor
ODD.
Options/Upgrades:
-
15 gallon waste tank and
alarm.
-
Automatic water drain into 15 gallon
container w/high level alarm.
-
3 Micron Spin - On Filter 1/2"
NOT w/gauge.
-
3 Micron Spin - On Filter 1"
NOT w/gauge.
-
Ethernet - PLC module, operator interface & 5 port.
-
Ethernet - field retrofit operation PLC module,
operator interface & 5 port.
Purifier heater.
-
Main disconnect breaker w/rotary handle (250)
(UL 508A w/42k
interrupt capacity.)
-
Main disconnect breaker w/rotary handle (480)
(UL 508A w/42k
interrupt capacity.)
-
MUDBUGS output.
-
Non-fused main disconnect switch w/rotary handle.
-
Secondary containment interface.
-
Strip heater for controller.
-
Thermostatically controlled system heater (touch pad,
controller purifier.)
-
Upgrade to 480VAC, 3 phase power.
-
115/120 Volt - 60 Hz.
-
208 Volt - 1 Phase - 60 Hz.
-
230 Volt - 1 Phase - 60 Hz.
-
208 Volt - 3 Phase - 60 Hz.
-
230 Volt - 3 Phase - 60 Hz.
-
380 Volt - 3 Phase - 50 Hz.
-
480 Volt - 3 Phase - 60
Hz.
|
|
|
Model FRS 660-RPU-UL
Designed for Single Tank
System / Rated at 40 GPM
Complete System is NEMA 4 UL 508A Listed
All closed cabinet models include the following
STANDARD features:
-
PLC
-
NEMA 4 UL 508A listed weatherproof
enclosure.
-
Powder coated white with key lock security.
-
6" weatherproof operator touch panel interface.
-
NPT brass inlet/outlet ball valves.
-
RCI Universal Fuel Purifier
-
Primary particulate
removal - 98% (to 10 microns.)
-
Free water removal -
99.9%.
-
Pre-engineered for Class II or III combustible
liquids.
-
Brass swing-check valves.
-
Manual key - auto / off / hand switch.
-
Common alarm reset button.
-
Common audible alarm.
-
System emergency shutdown points.
-
Recirculating pump with high pressure safety switch.
-
Water detector with Alarm and ball drain valve.
-
Catch basin leak detector.
-
Cabinet Leak Sensor and Alarm (Pump Shut Off.)
-
Magnetic Fuel Decontamination Unit.
-
Factory assembled, pre-plumbed and pre-wired.
-
Isolated compartments for
mechanical and electrical devices.
-
Expandable system.
Model FRS 660-11-UL Features :
-
42 " x 36 " x 12" Cabinet.
-
450 lbs. - Estimated shipping weight.
-
1" NPT Brass Inlet/Outlet Ball Valves.
-
1" NPT Brass Swing Check Valves.
-
1" NPT Brass Flow Meter.
-
FP 1000 - RCI Universal Fuel Purifier.
-
40 GPM.
-
Pump Motor Starter - 20
amp single pole circuit breaker.
-
115-208/230 VAC Single Phase, 60 Hz. motor ODP.
Options/Upgrades:
-
15 gallon waste tank and
alarm.
-
Automatic water drain into 15 gallon
container w/high level alarm.
-
3 Micron Spin - On Filter 1/2" NPT w/gauge.
-
3 Micron Spin - On Filter 1" NPT w/gauge.
-
Ethernet - PLC module, operator interface & 5 port.
-
Ethernet - field retrofit operation PLC module,
operator interface & 5 port.
Purifier heater.
-
Main disconnect breaker w/rotary handle (250)
(UL 508A w/42k
interrupt capacity.)
-
Main disconnect breaker w/rotary handle (480)
(UL 508A w/42k
interrupt capacity.)
-
MODBUS output.
-
Non-fused main disconnect switch w/rotary handle.
-
Secondary containment interface.
Strip heater for controller.
-
Thermostatically controlled system heater (touch pad,
controller purifier.)
-
Upgrade to 480VAC, 3 phase power.
-
115/120 Volt - 60 Hz.
-
208 Volt - 1 Phase - 60 Hz.
-
230 Volt - 1 Phase - 60 Hz.
-
208 Volt - 3 Phase - 60 Hz.
-
230 Volt - 3 Phase - 60 Hz.
-
380 Volt - 3 Phase - 50 Hz.
-
480 Volt - 3 Phase - 60
Hz.
|
 |
|
Model FRS 660-60-UL
Designed for Single Tank
System / Rated at 60 GPM
Complete System is NEMA 4 UL 508A Listed
All closed cabinet models include the following
STANDARD features:
-
PLC
-
NEMA 4 UL 508A listed weatherproof
enclosure.
-
Powder coated white with key
lock security.
-
6" weatherproof operator touch panel interface.
-
NPT brass inlet/outlet ball valves.
-
RCI Universal Fuel Purifier
-
Primary particulate
removal - 98% (to 10 microns.)
-
Free water removal -
99.9%.
-
Pre-engineered for Class II or III combustible
liquids.
-
Brass swing-check valves.
Manual key - auto / off / hand switch.
-
Common alarm reset button.
-
Common audible alarm.
-
System emergency shutdown points.
-
Recirculating pump with high pressure safety switch.
-
Water detector with Alarm and ball drain valve.
-
Catch basin leak detector.
-
Cabinet Leak Sensor and Alarm (Pump Shut Off.)
-
Magnetic Fuel Decontamination Unit.
-
Factory assembled, pre-plumbed and pre-wired.
-
Isolated compartments for
mechanical and electrical devices.
-
Expandable system.
Model FRS 660-11-UL Features :
-
Skid Mounted.
-
1050 lbs. - Estimated shipping weight.
-
2" NPT Brass Inlet/Outlet Ball Valves.
-
2" NPT Brass Swing Check Valves.
-
FP 1500 - RCI Universal Fuel Purifier.
-
60 GPM.
-
Pump Motor Starter - 20
amp single pole circuit breaker.
-
3 HP, 208-230/360 VAC Single Phase, 60 Hz. motor ODP.
-
2" Y strainer.
Options/Upgrades:
-
15 gallon waste tank and
alarm.
-
Automatic water drain into 15 gallon
container w/high level alarm.
-
3 Micron Spin - On Filter 1/2" NPT w/gauge.
-
3 Micron Spin - On Filter 1" NPT w/gauge.
-
Ethernet - PLC module, operator interface & 5 port.
-
Ethernet - field retrofit operation PLC module,
operator interface & 5 port.
Purifier heater.
-
Main disconnect breaker w/rotary handle (250)
(UL 508A w/42k
interrupt capacity.)
-
Main disconnect breaker w/rotary handle (480)
(UL 508A w/42k
interrupt capacity.)
-
MODBUS output.
-
Non-fused main disconnect switch w/rotary handle.
-
Secondary containment interface.
-
Strip heater for controller.
-
Thermostatically controlled system heater (touch pad,
controller purifier.)
-
Upgrade to 480VAC, 3 phase power.
-
115/120 Volt - 60 Hz.
-
208 Volt - 1 Phase - 60 Hz.
-
230 Volt - 1 Phase - 60 Hz.
-
208 Volt - 3 Phase - 60 Hz.
-
230 Volt - 3 Phase - 60 Hz.
-
380 Volt - 3 Phase - 50 Hz.
-
480 Volt - 3 Phase - 60
Hz.
|
 |
|
Model FRS 660-150-UL
Designed for Large Volume
Unit / Rated at 150 GPM
Complete System is NEMA 4 UL 508A Listed
All closed cabinet models include the following
STANDARD features:
-
PLC
-
NEMA 4 UL 508A listed weatherproof
enclosure.
-
Powder coated white with key lock security.
-
6" weatherproof operator touch panel interface.
-
NPT brass inlet/outlet ball valves.
-
RCI Universal Fuel Purifier
-
Primary particulate
removal - 98% (to 10 microns.)
-
Free water removal -
99.9%.
-
Pre-engineered for Class II or III combustible
liquids.
-
Brass swing-check valves.
-
Manual key - auto / off / hand switch.
-
Common alarm reset button.
-
Common audible alarm.
-
System emergency shutdown points.
-
Recirculating pump with high pressure safety switch.
-
Water detector with Alarm and ball drain valve.
-
Catch basin leak detector.
-
Cabinet Leak Sensor and Alarm (Pump Shut Off.)
-
Magnetic Fuel Decontamination Unit.
-
Factory assembled, pre-plumbed and pre-wired.
-
Isolated compartments for
mechanical and electrical devices.
-
Expandable system.
Model FRS 660-11-UL Features :
-
Skid Mounted.
-
1100 lbs. - Estimated shipping weight.
-
3" NPT Brass Inlet/Outlet Ball Valves.
-
3" NPT Brass Swing Check Valves.
-
FP 3000 - RCI Universal Fuel Purifier.
-
150 GPM.
-
Pump Motor Starter - 20
amp single pole circuit breaker.
-
5 HP, 230-3/60 VAC Single Phase, 60 Hz. motor ODP.
-
3 " Y strainer.
Options/Upgrades:
-
15 gallon waste tank and
alarm.
-
Automatic water drain into 15 gallon
container w/high level alarm.
-
3 Micron Spin - On Filter 1/2" NPT w/gauge.
-
3 Micron Spin - On Filter 1" NPT w/gauge.
-
Ethernet - PLC module, operator interface & 5 port.
-
Ethernet - field retrofit operation PLC module,
operator interface & 5 port.
-
Purifier heater.
-
Main disconnect breaker w/rotary handle (250)
-
(UL 508A w/42k
interrupt capacity.)
-
Main disconnect breaker w/rotary handle (480)
-
(UL 508A w/42k
interrupt capacity.)
-
MODBUS output.
-
Non-fused main disconnect switch w/rotary handle.
-
Secondary containment interface.
-
Strip heater for controller.
-
Thermostatically controlled system heater touch pad,
controller purifier.)
-
Upgrade to 480VAC, 3 phase power.
-
115/120 Volt - 60 Hz.
-
208 Volt - 1 Phase - 60 Hz.
-
230 Volt - 1 Phase - 60 Hz.
-
208 Volt - 3 Phase - 60 Hz.
-
230 Volt - 3 Phase - 60 Hz.
-
380 Volt - 3 Phase - 50 Hz.
-
480 Volt - 3 Phase - 60
Hz.
|
 |
You must have Adobe Reader to view PDF documents
from this site.
You can download Adobe Reader at the following
link:
Click here to view FRS660 brochure.
Model
FRS 660 Schematic
Multiple tank units can be
supplied with RCI Technologies innovated MODBUS ball valves
or conventional hard wired ball valves. The MODBUS requires
only 12 wires per system vs. converting 7 wires per valve.

Model
FRS 660-MTU 4 Tank Schematic
Multiple tank units can be
supplied with RCI Technologies innovated MODBUS ball valves
or conventional hard wired ball valves. The MODBUS requires
only 12 wires per system vs. converting 7 wires per valve.

Back to top of page |